excel sheet for heat pump registers now in template form. tested with script that was also added in folder. sg-ready testing file was also added.

This commit is contained in:
Nils Reiners
2026-01-06 17:01:50 +01:00
parent ce14d59d51
commit 8642a057f0
6 changed files with 214 additions and 45 deletions

View File

@@ -0,0 +1,7 @@
from heat_pump import HeatPump
hp_master = HeatPump(device_name='hp_master', ip_address='10.0.0.10', port=502, excel_path="../modbus_registers/heat_pump_registers.xlsx")
state = hp_master.get_state()
print(state)

View File

@@ -0,0 +1,49 @@
from pymodbus.client import ModbusTcpClient
def switch_sg_ready_mode(ip, port, mode):
"""
Register 300: 1=BUS 0= Hardware Kontakte
Register 301 & 302:
0-0= Kein Offset
0-1 Boiler und Heizung Offset
1-1 Boiler Offset + E-Einsatz Sollwert Erhöht
1-0 SG EVU Sperre
:param ip:
:param mode:
'mode1' = [True, False, False] => SG Ready deactivated
'mode2' = [True, False, True] => SG ready activated for heatpump only
'mode3' = [True, True, True] => SG ready activated for heatpump and heat rod
:return:
"""
client = ModbusTcpClient(ip, port=port)
if not client.connect():
print("Verbindung zur Wärmepumpe fehlgeschlagen.")
return
mode_code = None
if mode == 'mode1':
mode_code = [True, False, False]
elif mode == 'mode2':
mode_code = [True, False, True]
elif mode == 'mode3':
mode_code = [True, True, True]
else:
print('Uncorrect or no string for mode!')
try:
response_300 = client.write_coil(300, mode_code[0])
response_301 = client.write_coil(301, mode_code[1])
response_302 = client.write_coil(302, mode_code[2])
# Optional: Rückmeldungen prüfen
for addr, resp in zip([300, 301, 302], [response_300, response_301, response_302]):
if resp.isError():
print(f"Fehler beim Schreiben von Coil {addr}: {resp}")
else:
print(f"Coil {addr} erfolgreich geschrieben.")
finally:
client.close()
if '__name__' == '__main__':
switch_sg_ready_mode(ip='10.0.0.10', port=502, mode='mode2')