Files
allmende_ems/test_meter.py
2025-09-16 22:46:42 +02:00

62 lines
1.8 KiB
Python

#!/usr/bin/env python3
# -*- coding: utf-8 -*-
from pymodbus.client import ModbusTcpClient
import struct, sys
MODBUS_IP = "192.168.1.112"
MODBUS_PORT = 502
UNIT_ID = 1
METER_START = 40240 # Startadresse Model 203-Felder
def to_i16(u16): # unsigned 16 → signed 16
return struct.unpack(">h", struct.pack(">H", u16))[0]
def read_regs(client, addr, count):
rr = client.read_holding_registers(address=addr, count=count, slave=UNIT_ID)
if rr.isError():
return None
return rr.registers
def read_meter_power(client):
base = METER_START
p = read_regs(client, base + 16, 1) # M_AC_Power
pa = read_regs(client, base + 17, 1) # Phase A
pb = read_regs(client, base + 18, 1) # Phase B
pc = read_regs(client, base + 19, 1) # Phase C
sf = read_regs(client, base + 20, 1) # Scale Factor
if not p or not sf:
return None
sff = to_i16(sf[0])
return {
"total": to_i16(p[0]) * (10 ** sff),
"A": to_i16(pa[0]) * (10 ** sff) if pa else None,
"B": to_i16(pb[0]) * (10 ** sff) if pb else None,
"C": to_i16(pc[0]) * (10 ** sff) if pc else None,
"sf": sff
}
def fmt_w(v):
if v is None: return "-"
neg = v < 0
v = abs(v)
return f"{'-' if neg else ''}{v/1000:.2f} kW" if v >= 1000 else f"{'-' if neg else ''}{v:.0f} W"
def main():
client = ModbusTcpClient(MODBUS_IP, port=MODBUS_PORT)
if not client.connect():
print("❌ Verbindung fehlgeschlagen."); sys.exit(1)
try:
m = read_meter_power(client)
if m:
print(f"Meter-Leistung: {fmt_w(m['total'])} "
f"(A {fmt_w(m['A'])}, B {fmt_w(m['B'])}, C {fmt_w(m['C'])}) [SF={m['sf']}]")
else:
print("Meter-Leistung konnte nicht gelesen werden.")
finally:
client.close()
if __name__ == "__main__":
main()